Installation Testing Maintenance Instructions
Proposition 65 Warning This product contains chemicals known to the State
of California to cause cancer or birth defects or other reproductive harm.
Model 70XL LEAD-FREE*
Pressure Reducing Valve with Integral By-pass (3/4” & 1”)
®
REPAIR KIT INSTRUCTIONS
HOW TO MAKE REPAIRS:
(Shut off service before starting disassembly)
1. Open faucet on dwelling to remove line pressure.
2. Note distance that adjustment bolt protrudes from bell housing.
Loosen locknut on adjustment bolt, then turn adjustment
bolt out of bell housing to remove spring tension.
3. Unscrew bell housing counterclockwise and remove spring,
spring disc and friction ring.
4. While holding diaphragm, unscrew diaphragm bolt counter-
clockwise and remove bolt, diaphragm disc and diaphragm.
5. Remove cartridge counterclockwise; Use a 1-1/8” socket for
the 3/4” and a 1-3/8” socket for the 1”. Make sure
cartridge gasket is removed from the body.
TO REASSEMBLE:
1.Whiledisassembled,openinletofwaterservicetoushout
valve body and service line of debris.
2. Lubricate o-ring on replacement cartridge then thread into
body clockwise.
3. Replace diaphragm, diaphragm disc and diaphragm bolt (It is
necessary to hold diaphragm while tightening diaphragm
bolt.).
4. Replace friction ring, spring, spring disc and bell housing.
Tighten bell housing onto body by threading clockwise.
5. Turn adjustment bolt into bell housing to old setting.
6. Enter dwelling and turn on several faucets.
7. Turn on water service. Let water run for several seconds then
turn off faucets in dwelling.
8. Adjust regulator to desired pressure by turning adjusment
bolt clockwise (into bell housing) to raise pressure or
counterclock-wise (out of bell housing) to lower pressure.
It is recommended a pressure gauge be installed down
stream of the regulator to ensure pressure is reduced
below 75 psi. NOTE: When reducing pressure, open a down
stream faucet to relieve pressure.
9. Tighten locknut when desired pressure is achieved.
INSTALLATION INSTRUCTIONS
Install valve in line with arrow on valve body pointing in direction of
ow.Beforeinstallingreducingvalve,ushoutlinetoremoveloose
dirt and scale which might damage seal ring and seat. All valves
will be furnished with stock settings to reduce to 50 psi. To readjust
reduced pressure, loosen outer locknut and turn adjustment bolt
clockwise (into bell housing) to raise reduced pressure, or coun-
terclockwise (out of bell housing) to lower reduced pressure.
NOTICE: Annual inspection and maintenance is required of all
plumbing system components. To ensure proper performance
and maximum life, this product must be subject to regular
inspection, testing and cleaning.
Regulators in series: Where the desired pressure reduction
is more than a 4 to 1 ratio (i.e. 200psi to 50psi), multiple
regulators in series should be installed.
SEALED CAGE WARNING: Loosen lock washer at adjustment
bolt slowly. Look for any trapped water pressure under the
sealed cage washer. Relieve pressure before removing bell.
CAUTION: Anytime a reducing valve is adjusted, a pressure
gauge must be used downstream to verify correct pressure
setting. Do not bottom out adjustment bolt on bell housing.
Valve may be installed in any position.
*This product contains a weighted average lead content less than 0.25% for wetted surfaces.
W
S
K
I
L
N
I
UNION NUT
TAILPIECE
BODY
*SPRING DISC
NAMEPLATE
ADJUSTMENT
BOLT
*UNION GASKET
*CARTRIDGE
*SPRING
LOCKNUT
*DIAPHRAGM
SEALED CAGE
WASHER
*SEAL RING
BELL
HOUSING
*DIAPHRAGM
DISC
*CARTRIDGE GASKET
70XL
*DIAPHRAGM BOLT
*FRICTION RING
*INDICATES PARTS SUPPLIED IN REPAIR KITS
1
®
WARRANTY: ZURN WILKINS Valves are guaranteed against defects of material or workmanship when used for the services recommended. If
in any recommended service, a defect develops due to material or workmanship, and the device is returned, freight prepaid, to ZURN WILKINS
within 12 months from date of purchase, it will be repaired or replaced free of charge. ZURN WILKINS’ liability shall be limited to our agreement
to repair or replace the valve only.
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Model 70XL LEAD-FREE*

 Installation  Testing  Maintenance InstructionsProposition 65 Warning This product contains chemicals known to the State of California to cause ca

Page 2 - Troubleshooting

TroubleshootingPipelinesinawatersupplysystemmustbeofsufcientcar-rying capacity to maintain adequate pressure at the most remote or hi

Commentaires sur ces manuels

Pas de commentaire